Top

Zoom

Description

Honeywell ECC-FFT - Fire Fighter Telephone

General:

Firelite’s ECC-FFT is a Fire Fighter telephone system that provides secure and reliable communications for firefighters. This standalone system is capable of providing annunciation and control for local and remote telephone handsets. It includes a built in display and keypad that provide an indication of phone activation as well as corresponding trouble conditions. For added flexibility, 24 remote telephone connections are offered that can be monitored individually or as a group of multi-phone jacks. The auto-program feature automatically recognizes all existing fire fighter phone jacks on the system and immediately configures the system for full operation and supervision.

The ECC-FFT allows for up to ten users to plug in to a remote telephone jack (FPJ-F) and communicate simultaneously within a building. An onboard SLC circuit (capable of being wired in Class B (Style 4) or Class A (Style 6)) allows for continuous monitoring of the telephone jacks connected to the system. It is housed in a lockable cabinet that includes multiple knockout locations for field wiring.

Typical Application:

  • Schools

  • Healthcare Facilities

  • Factories

  • Theaters

  • Military facilities

  • Restaurants

  • Auditoriums

  • Places of Worship

  • Office Buildings

  • Dormitories

Features:

  • Provides supervision control and annunciation of up to 24 remote telephone jacks.

  • Built-in Auto-program feature.

  • Simple and straightforward user interface.

  • Telephone circuit supervised with 4.7KΩ, End of line resistor when wired in Style Y, Class B operation.

  • Full System status LED display.

  • Onboard SLC circuit can be wired for class A (Style 6 or Style 7) or class B (Style 4) configuration.

  • Full system status LED display.

  • Supports Multi-Phone Jack Audio Circuit supervision.

  • Onboard Form-C system trouble relay.

  • Allows simultaneous operation of up to 10 Fire Fighter remote handsets (FHS-F when connected to the ECC-FFT.

  • Fire Fighter Phone Jack (FPJ-F provides a plug-in location for the FHS-F.

  • Fire Fighter Handset Cabinet (FHSC-RF/SF) is used to store five Fire Fighter Handsets (FHS-F).

Optional Accessories:

  • FPJ-F: Remote Phone Jack which mounts to a single-gang electrical box.

  • FHS-F: Fire Fighter Handset used to communicate over the telephone circuit connected to the ECC-FFT.

  • FHSC-RF: Fire Fighter Handset Cabinet (recess mount) is used to store five Fire Fighter Handsets (FHS-F).

  • FHSC-SF: Optional Fire Fighter Handset Cabinet (surface mount) is used to store five Fire Fighter Handsets (FHS-F).

  • MMF-301: Addressable monitor module that can be used to monitor the connection of the Fire Fighter Telephone remote handset (FHS-F). Up to 24 of these modules are supported by the ECC-FFT.

  • I300: Fault Isolator module used to protect the ECC-FFT against wire-to-wire short circuits on the SLC loop. It is placed between each device or the SLC loop to isolate a short-circuit problem between the Remote Phone Jacks (FPJ-F) when Class A (Style 7) wiring is required

Control and indicators

PUSH BUTTON CONTROLS

  • Auto-program: Searches the SLC loop on the ECC-FFT for devices. When a device is found, the active LED will blink in each zone.

  • Accept: Used to accept the configuration after an auto-program is initiated.

  • Answer Call: Will connect the local handset to a phone circuit for communication when a remote handset is plugged into a (FPJ-F phone jack.

  • Trouble Silence: Used to silence a system type trouble that has occurred in the ECC-FFT system.

 

Decision Supporter

Verified Supplier
Member Since
June 2017

Specs

Electrical Specifications

PRIMARY POWER REQUIREMENTS:

  • Voltage 24VDC (nominal) power limited, filtered, non-resettable.
  • Voltage Range for operation: 17-29 VDC.
  • Current Requirements:

Standby: 120mA.  

Active: 230mA.

ELECTRICAL RATINGS

  • SLC circuit:

-       Voltage output: 32VDC. Current rating: 150mA.

  • Audio Circuit:

-       Voltage output: 17VDC. Current rating: 53mA.